Boiler Data
Steam Output
5,175 lbs/hr from and at 212 degrees F
Emissions
30 PPM Low NOx Burner
Fuels
Natural Gas and Light Oil
Connections
City Water
1” NPT
Natural Gas
3” 150# Flanged
Fuel Oil Supply
3/4” NPT
Fuel Oil Return
3/4” NPT
Steam
3“ 300# Flanged
Blowdown Drain
4” 300# Flanged
Requirements
Electrical
60 AMPS @ 460/3/60HZ
Atomizing Air
Air Compressor, Included
Instrument Air
Not Required
Fuel Oil Pump
Included
Stub Stack
Included
Gas CFH (1,000 BTU)
6,124 CFH
Gas Pressure
5-10 PSIG with Regulator. 1-3 psig w/out
Light Oil GPH (140,000 BTU/gallon)
43.7 GHP
City Water
55 gallons per minute, 40-90 psi
Water Softener
Included
Chemical Feed Tank
Included
Blowdown Separator
Included, with aftercooler
Feedwater tank, triplex (3 pumps):
Included